The original code uses raw file or archive helpers. TIA Portal restricts PLC file I/O to specific SIMATIC Memory Card instructions, and no native compression block exists for LZMA/archive behavior. Do not emit raw FIL...

Public manifest facts

id
file_io_archives_to_datalog_or_db
category
File/Archive Helpers
severity
architectural_change
context summary
The original code uses raw file or archive helpers. TIA Portal restricts PLC file I/O to specific SIMATIC Memory Card instructions, and no native compression block exists for LZMA/archive behavior. Do not emit raw FIL...
trigger keyword count
21
sample trigger keywords
FILE_OPEN, FILE_CLOSE, FILE_CREATE, FILE_DELETE, FILE_RENAME, FILE_GET_INFO, FILE_COMPRESS, FILE_SYS_FREE_SPACE, FOPEN, FWRITE, FILE_READ, FileOpen
siemens equivalents
DataLogCreate, DataLogOpen, DataLogWrite, DataLogClose, DataLogClear, FileReadC, FileWriteC, FileDelete
bundle callable refs
datalogcreate, datalogopen, datalogwrite, datalogclose, datalogclear