Knowledge / Semantic rule
timestamp_clock_helpers
The original code attempts to read the current clock using generic CODESYS/TwinCAT/helper-style names. Siemens S7-1200/S7-1500 SCL does not support simple NOW() or DT_NOW() expressions. Prefer an existing project time...
Public manifest facts
- id
- timestamp_clock_helpers
- category
- Timestamp/Clock Helpers
- severity
- minor_refactor
- context summary
- The original code attempts to read the current clock using generic CODESYS/TwinCAT/helper-style names. Siemens S7-1200/S7-1500 SCL does not support simple NOW() or DT_NOW() expressions. Prefer an existing project time...
- trigger keyword count
- 39
- sample trigger keywords
- NOW, now, DT_NOW, GETDT, GET_DT, GET_DATE_AND_TIME, GET_CURRENT_DATE_AND_TIME, GET_CURRENT_DATE_TIME, GET_CURRENT_DATEANDTIME, GET_CUR_DATE_AND_TIME, GET_CUR_DATE_TIME, GET_CUR_DT
- siemens equivalents
- RD_SYS_T, RD_LOC_T, DTL#1970-01-01-00:00:00
- bundle callable refs
- rd_sys_t, rd_loc_t
- source path
- knowledge/semantic_rules.yaml